Guides
Compatibility List
AI Assistant
Troubleshooting (FAQ)

More energy meters on a single Modbus RTU bus

Configuration of multiple energy meters connected to a single Modbus RTU bus

Steps for configuring energy meters

  1. Unbind the bus terminal

    • Go to SettingsHardware → TapHome Bus.
    • Unbind the bus terminal to which the energy meters are connected.
  2. Add new interface

    • Go to SettingsHardwareAdd new interface → Modbus RTU.
    • Go to Add from template , locate your energy meter and select Add .
  3. Assign the terminal

    • Open the meter details.
    • At the top, go to Terminals and assign Bus1, Bus2 or Bus3.
  4. Connect the meters one by one

    • Do not connect all meters at once; start with the first meter. 1.png
  5. For the first meter, assign a high Slave ID

    • Avoid setting the Slave ID to 1 (the default value from the factory).
    • Example: If you have 5 meters, set the Slave ID of the first meter to 5.
  6. Adjust the Slave ID in the service settings

    • Click on Service settings .
    • Scroll down and click on Slave ID (the service action “Slave ID”, not the module communication setting).
    • Assign the value 5 (if you are configuring 5 meters).
    • Save Service settings . 2.png
  7. Connect the second meter

    • Now connect the second meter to the same bus as the first meter.
    • Repeat the same sequence:
      • Set a higher Slave ID
      • Go to Service settings
      • Scroll down
      • Click on Slave ID
      • Assign the value 4 (if this is the second of 5 meters).
  8. Repeat for the remaining meters

    • Continue configuring each meter one by one, following the same procedure.